  • Max 256 indoor units (4 systems x 64 units) can be controlled. In case of three or more systems (more than 128 units), a communication adapter must be installed
  • Operation is possible as batch, in zone units, in tenant and in group units

  • ON/OFF, operation mode setting, temperature setting, for fan speed setting, air flow direction setting (when used without a remote controller), and remote controller local operation prohibition (prohibition 1, 2, 3, 4) can be done

  • A system without a remote controller is possible. Joint use with a remote controller or a system controller is also possible
  • Use of a schedule timer and holiday setting also can be done

  • Pulse signal input from electric/gas consumption meter
In case of joint use with a wireless remote control system, there are limitations for the control mode. Please use only with “Permission” and “Prohibition 1”.

• Limitation contents for prohibited operation
Prohibition means limitation of the operation contents from the remote controller.
It is also possible to change the prohibition items.
Individual
There is no limitation for the operation of the remote controller. However, the contents will be changed to the contents of the controller operated last. (Last-pressed priority.)

Prohibition 1
The remote controller cannot be used for ON/OFF. (All other operations are possible from the remote controller.)

Prohibition 2
The remote controller cannot be used for ON/OFF, operation mode change and temperature setting. (All other operations are possible from the remote controller.)
Prohibition 3
The remote controller cannot be used for operation mode change and temperature setting. (All other operations are possible from the remote controller.)


Prohibition 4
The remote controller cannot be used for operation mode change. (All other operations are possible from the remote controller.)



 *Required when more than 129 indoor units are connected.